Home / Services / Water Improvement Plans

Water Improvement Plans

Water improvement plans are the engineering document set governing how potable water service and often fire protection water gets from the public water system to a project, along with any new public water infrastructure a development is required to build or upsize along the way. Where a utility plan might show a water line as a single element connecting a meter to a main, water improvement plans go into the depth a water agency actually requires to approve construction within its system: pipe sizing based on demand and fire flow, material specifications, valve and hydrant placement, and connection details to existing infrastructure.

Trusted By:

Like sewer improvement plans, this becomes its own distinct deliverable specifically when a project needs to extend, loop, or upsize the public water system not simply tap into an adequately sized existing main. A single home connecting to an existing main at the curb is a standard utility connection. A subdivision extending new water mains through an internal street network, or a commercial project requiring upsized mains to meet fire flow requirements, is public water infrastructure built by a private developer, and it’s reviewed with that in mind.

What water improvement plans actually cover

A complete set of water improvement plans shows the horizontal alignment and depth of proposed water mains, sized against a combined domestic demand and fire flow calculation rather than an assumed standard diameter. It specifies pipe material and class appropriate to the system’s operating pressure, along with valve placement and spacing set by a jurisdiction’s standard for isolating sections of main during repair or emergency shutoff. 

It includes fire hydrant locations and spacing, typically governed by fire department standards tied to hydrant coverage radius and required fire flow for the specific land use, and shows connection points and any required looping back into the existing system many agencies specifically require looped rather than dead-end mains beyond a certain length, since dead ends create water quality issues from stagnation as well as firefighting limitations. Where water lines cross or run parallel to sewer or storm drain infrastructure, plans document the specific separation and crossing details most agencies require to protect potable water from contamination.

For projects at higher elevations or serving larger developments, this scope sometimes extends into pressure zone analysis and, where gravity pressure alone isn’t adequate, booster pump station design.

Why fire flow drives more of this than people expect

Domestic demand the water a building actually uses day to day is often the smaller number in the sizing calculation. Fire flow, the volume and pressure a fire department requires to be available at a hydrant near the project, frequently governs pipe sizing instead, particularly for commercial, multi-family, or larger residential projects where required fire flow substantially exceeds domestic demand. 

This is also why water improvement plans are rarely finalized without fire department input: the specific fire flow requirement, hydrant spacing, and sometimes fire department connection location are set by the local fire authority, not the water agency, adding a third technical reviewer to a document that might otherwise seem like a straightforward utility exercise.

How this connects to the rest of the project

Water improvement plans have to coordinate closely with sewer and storm drain design running through the same street corridor, since all three utilities compete for the same trench space and have to be sequenced with proper vertical and horizontal separation. They also depend on the site’s grading and building layout for meter and service line placement, and on the architectural design for the building’s actual fire flow requirement, which is calculated from occupancy type and square footage rather than assumed generically. A change late in design an added building, a shift in occupancy classification can change the required fire flow enough to require a different main size than what was originally planned.

Agency review in California

Water improvement plans are typically reviewed by the specific water utility serving the site which may be a municipal water department, an independent water district, or in some areas a private water company separate from the city’s building department review of the rest of the project. Fire flow and hydrant requirements are reviewed independently by the local fire authority, meaning a project can face two distinct technical reviews on the same set of plans. Some agencies require a capacity or pressure analysis of the existing system before approving a new connection, particularly in areas with older infrastructure or at the edge of a pressure zone, and may require developer-funded upsizing as a condition of service.

When you need this

Any project extending new water mains, upsizing existing ones, or requiring fire flow beyond what an existing system can currently deliver needs water improvement plans as part of its civil package. This is typical on new subdivisions, larger commercial and multi-family developments, and any project where the serving water agency or fire authority determines existing infrastructure needs modification to meet demand and fire flow requirements. Smaller projects connecting to an adequately sized existing main usually don’t need this as a standalone deliverable.

Frequently asked questions

Usually not as a separate deliverable. This level of detail typically applies when a project extends new water mains, upsizes existing infrastructure, or triggers a fire flow requirement the existing system can't currently meet a straightforward connection to an adequately sized main is usually handled within the standard utility plan instead.

Required fire flow is often larger than domestic demand, particularly for commercial or multi-family buildings, and frequently governs pipe sizing as a result. The specific requirement comes from the local fire authority based on occupancy type and building size, not from how much water the building will use day to day.

Typically the specific water utility serving the site which could be a city water department, an independent water district, or a private water company along with a separate review from the local fire authority for fire flow and hydrant requirements. That's often two distinct reviewers on the same set of plans.

Dead-end mains can cause water quality issues from stagnant water and provide less reliable pressure for firefighting. Many agencies require new mains to loop back into the existing system beyond a certain length specifically to avoid both problems.

Yes. Adding a building or changing an occupancy classification can change the required fire flow, which may require a different main size than originally planned. Water improvement plans are typically finalized only once the building program is settled for this reason.

Where we start

We begin by identifying the specific water agency and fire authority serving the site, then calculate domestic demand and required fire flow based on the proposed land use and building occupancy. Send us the project address and proposed building program, and we’ll confirm what your serving agency and fire authority will require, along with a fee and schedule in writing.

2102 Business Center Drive, Suite 130, Irvine, CA 92612