Commercial Kitchen Exhaust and Makeup Air Requirements in California

Exhaust fan in a sheet metal housing on the roof of a commercial building

A commercial kitchen in California needs a Type I hood over cooking appliances that produce grease or smoke, an exhaust system that carries the vapors outside, and makeup air that replaces what the hoods exhaust. The California Mechanical Code sets the hood, duct and makeup air rules. The Energy Code limits how much heated and cooled air the system may use, and the Fire Code adds a fire-extinguishing system for Type I hoods.

This guide follows the 2025 California codes, in effect since January 1, 2026. It was checked on November 23, 2026 against the sources listed at the end.

Who reviews a kitchen ventilation design

  • The building department. Mechanical plan check against Chapter 5 of the California Mechanical Code, and the Energy Code forms.
  • The fire department. The fire-extinguishing system that protects the hood and duct.
  • The environmental health department. Food facility plan check. The County of Los Angeles, for example, asks for a data sheet for each hood with the equipment under it and its filters.

Type I and Type II hoods

  • Type I. Required for cooking appliances that produce grease or smoke, under Section 508.1.
  • Type II. For equipment and dishwashers that give off steam, heat or products of combustion without grease or smoke, under Section 519.1.

Section 508.1 has exceptions. A Type I hood is waived for listed reduced-emission appliances whose grease discharge stays under the limit in the code, and for listed recirculating systems installed under Section 516.0. These are the appliances usually sold as ventless. San Francisco's building department notes that an appliance of the first kind still needs a listed fire-extinguishing system when it has none built in, so it helps to show the listing of each appliance on the plans.

Makeup air

Every cubic foot of air a hood exhausts has to be replaced. Section 511.3 of the Mechanical Code sets the rules:

  • Pressure. Makeup air has to keep the negative pressure in the cooking area at or below 0.02 inch of water column.
  • Compensating hoods. Makeup air supplied inside the hood is limited to 10 percent of the exhaust airflow.
  • Fire. Makeup air supplied inside the hood shuts off when the fire-extinguishing system activates.
  • Air balance. The plans include an outdoor air balance showing that total replacement air equals total exhaust plus net exfiltration.

The air balance ties the hoods, the makeup air unit, the dining room air handlers and the restroom exhaust into one table, so every source of exhaust and replacement air in the space is accounted for.

Where the exhaust terminates

For a Type I system that terminates on the roof, Section 510.9.1 sets the clearances:

  • 10 feet horizontally from the outlet to adjacent buildings, property lines and air intakes.
  • 5 feet horizontally from the outlet or fan housing to any combustible structure.
  • 3 feet of vertical separation above air intakes within 10 feet of the outlet.
  • For hinged upblast fans, a discharge at least 40 inches above the roof.
  • Grease drained to a closed, noncombustible, rainproof container.

On a tenant improvement in an existing building, these clearances decide where the fan can go. They are worth checking against the roof plan before the kitchen layout is fixed.

Fan operation and testing

The exhaust fan has to start when any heat-producing appliance under the hood is turned on. Before final approval, the code calls for a performance test that verifies the exhaust airflow, and a capture and containment field test for Type I hoods at operating temperatures and design airflows.

What the Energy Code adds

Section 140.9(b) of the 2025 Energy Code sets prescriptive requirements for commercial kitchens. Healthcare facilities are excepted.

  • Short-circuit air. Replacement air introduced directly into the hood cavity is limited to 10 percent of the hood exhaust airflow.
  • Conditioned makeup air. Mechanically heated or cooled makeup air is capped at the greater of two values: the supply air the space needs for its heating and cooling load, or the hood exhaust minus the transfer air available from adjacent spaces.
  • Large kitchens. Where the Type I and Type II hoods together exhaust more than 5,000 cubic feet per minute, each Type I hood has to stay within the exhaust rates of Table 140.9-C, and the facility has to use one of four measures.
Measure for kitchens above 5,000 cfmThreshold
Transfer airAt least 50 percent of all replacement air is transfer air.
Demand ventilationOn at least 75 percent of the exhaust air, with airflow that follows appliance operation.
Energy recoveryListed devices with at least 40 percent sensible heat recovery effectiveness on at least 50 percent of the total exhaust airflow.
Tempered makeup airAt least 75 percent of the makeup air is unheated or heated to no more than 60 degrees Fahrenheit, and uncooled or cooled without mechanical cooling.

Existing hoods and existing makeup air units that are not replaced as part of an addition or alteration are excepted from these requirements. Before the occupancy permit, the kitchen exhaust system has to pass its acceptance test, and the certificate of acceptance, form NRCA-PRC-02-F, goes to the building department.

Fire protection

A hood and duct system that requires a Type I hood has to be protected by an approved automatic fire-extinguishing system. Fire agencies cite Sections 904.5 and 904.14 of the 2025 California Fire Code for it. The system has its own listing and its own review, so ask the fire department how it wants the submittal made.

Examples from our projects

On a restaurant tenant improvement in Costa Mesa, a change to restaurant use drove the mechanical design: the kitchen ventilation and exhaust hoods, the makeup air systems and the equipment layout. On a commercial kitchen tenant improvement in San Diego, the mechanical scope covered the kitchen ventilation and exhaust design, the exhaust fans and roof terminations, the rooftop equipment layout and the mechanical code analysis.

Common questions

When is a Type I hood required?

Over cooking appliances that produce grease or smoke, unless the appliance falls under one of the listed exceptions in Section 508.1.

How much makeup air does a commercial kitchen need?

Enough to keep the negative pressure in the cooking area at or below 0.02 inch of water column. The plans show it in an air balance of replacement air against exhaust.

Can makeup air come from the dining room?

Yes. The Energy Code calls it transfer air, and it limits conditioned makeup air by the amount of transfer air available.

Do the Energy Code rules apply to an existing hood?

Existing hoods and makeup air units that are not replaced as part of an addition or alteration are excepted from Section 140.9(b).

How far must a kitchen exhaust fan be from the property line?

For a rooftop termination, 10 feet horizontally from the outlet to property lines, adjacent buildings and air intakes.

Does a ventless appliance need a hood?

A listed recirculating system or reduced-emission appliance can be exempt from the Type I hood. The listing and the fire-extinguishing provisions still have to be shown.

How we help

We prepare the mechanical, electrical and plumbing plans for restaurants and commercial kitchens, including the HVAC and kitchen ventilation design and the Title 24 compliance documents. We prepare the compliance forms. Acceptance testing in the field is not part of our scope. Related reading: HVAC permit requirements in California.

Sources

Checked November 23, 2026. This article is general information, not advice for a specific project. Requirements change over time, and local amendments apply, so confirm them with the building, fire and health departments that will review your plans.